| Parameter name | Unit | Value |
Rated voltage |
kV | 12 |
Rated normal current |
A | 630 |
Rated frequency |
Hz | 50 |
Rated active load breaking current |
A | 630 |
Rated loop-locked breaking current |
A | 630 |
Rated short-time withstand current |
kA | 20 |
Rated short-circuit continuous time |
S | 3 |
Rated peak withstand current |
kA | 20 |
Rated short-time (1 min) frequency withstand voltage |
kV | 42 |
Rated electric cable be charged breaking current |
A | 10 |
Rated short-circuit making current |
kA | 50 |
Rated lightning impulse withstand voltage |
kV | 75 |
Rated contact pressure time-limit loop resistive |
µn | ≤40 |
Mechanical life |
10000 | |
Contact automatic |
N | 40±20 |
Force required to hold contacts open at full stroke |
N | 70±20 |
Contact-wear allowance thickness |
Mm | 3 |
Internal gas pressure |
Pa | ≤1.33×10-3 |
Shelf life |
20 |