• Professional Manufacturer Of Vacuum interrupter,Vacuum tube etc.
  • China mining light
  • Products

Load switch used vacuum interrupter

  • Type: TF-12/630-20(BGE702)

  • Vacuum Tube main technique parameter
  • Parameter name Unit Value
    Rated voltage kV 12
    Rated normal current A 630
    Rated frequency Hz 50
    Rated active load breaking current A 630
    Rated loop-locked breaking current A 630
    Rated short-time withstand current kA 20
    Rated short-circuit continuous time S 3
    Rated peak withstand current kA 20
    Rated short-time (1 min) frequency withstand voltage kV 42
    Rated electric cable be charged breaking current A 10
    Rated short-circuit making current kA 50
    Rated lightning impulse withstand voltage kV 75
    Rated contact pressure time-limit loop resistive  µn ≤40
    Mechanical life   10000
    Contact automatic N 40±20
    Force required to hold contacts open at full stroke N 70±20
    Contact-wear allowance thickness Mm 3
    Internal gas pressure Pa ≤1.33×10-3
    Shelf life   20