| Using Area | Capacitor (R) | |||
| Product Model | HY5WR-5/13.5 | HY5WR-10/27 | HY5WR-17/46 | |
| Lightning Arrester Rating voltage virtual value(KV) | 5 | 10 | 17 | |
| System nominal voltage virtual value(KV) | 3 | 6 | 10 | |
| Continuous working voltage virtual value(KV) | 4.0 | 8.0 | 13.6 | |
| DC(U1mA)Ref.Voltage no less than(KV) | 7.2 | 14.4 | 24 | |
| Max.residual voltage Peak value(KV) | Teep ware impulse current | -- | -- | -- |
| Lighting impulse current | 13.5 | 27 | 45 | |
| Operating impulse current | 10.5 | 21.0 | 35.0 | |
| 2000μs Square wave flux capacity(A) | 400 | 400 | 400~1000 | |
| 4/10 μs Impulse current peak value(kA) | 65 | 65 | 65 | |
| Max.Leaking current under 0.75DC ref.Voltage(μA) | 30 | 30 | 30 | |